Delta Electronics VFD-E manual Factory Setting

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 91
Image 91
Factory Setting: 0

Chapter 4 Parameters

This parameter allows the user to reset all parameters to the factory settings except the fault records (Pr.06.08 ~ Pr.06.12).

50Hz: Pr.01.00 and Pr.01.01 are set to 50Hz and Pr.01.02 will be set by Pr.00.12.

60Hz: Pr.01.00 and Pr.01.01 are set to 60Hz and Pr.01.02 is set to 115V, 230V or 460V. When Pr.00.02=1, all parameters are read-only. To write all parameters, set Pr.00.02=0.

00.03Start-up Display Selection

 

Factory Setting: 0

Settings 0

Display the frequency command value (Fxxx)

1

Display the actual output frequency (Hxxx)

2

Display the output current in A supplied to the motor

 

(Axxx)

3

Display the content of user-defined unit (Uxxx)

4

FWD/REV command

5

PLCx (PLC selections: PLC0/PLC1/PLC2)

 

(NOT for VFD*E*C models)

This parameter determines the start-up display page after power is applied to the drive.

For setting 5, PLC0: disable, PLC1: run PLC, PLC2: read/write PLC programs into AC motor drive.

00.04Content of Multi-function Display

Settings 0

Display the content of user-defined unit (Uxxx)

 

 

1

Display the counter value which counts the number of

 

 

 

pulses on TRG terminal

 

 

 

 

 

2

Display PLC D1043 value (C)

 

 

 

(NOT for VFD*E*C models)

 

 

 

 

 

3

Display the actual DC BUS voltage in VDC of the AC

 

 

 

motor drive

 

 

4

Display the output voltage in VAC of terminals U/T1,

 

 

 

V/T2, W/T3 to the motor.

 

 

 

 

5

Display PID analog feedback signal value in %

 

 

 

 

 

 

4-38

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 91
Image 91
Delta Electronics VFD-E manual Factory Setting