Chapter 4 Parameters

03.08

Fan Control

 

 

 

 

 

Factory Setting: 0

 

Settings

0

Fan always ON

 

 

1

1 minute after AC motor drive stops, fan will be OFF

 

 

2

Fan ON when AC motor drive runs, fan OFF when AC motor drive

 

 

 

stops

 

 

3

Fan ON when preliminary heatsink temperature attained

 

 

 

 

This parameter determines the operation mode of the cooling fan.

03.09The Digital Output Used by PLC (NOT for VFD*E*C models)

Settings Read Only

Factory setting: ##

Bit0=1: RLY used by PLC

 

Bit1=1: MO1 used by PLC

 

Bit2=1: MO2/RA2 used by PLC

Bit3=1: MO3/RA3 used by PLC

Bit4=1: MO4/RA4 used by PLC

Bit5=1: MO5/RA5 used by PLC

Bit6=1: MO6/RA6 used by PLC

Bit7=1: MO7/RA7 used by PLC

The equivalent 8-bit is used to display the status (used or not used) of each digital output. The value that Pr.03.09 displays is the result after converting 8-bit binary into decimal value.

For standard AC motor drive, it only has 2-bit (bit0 and bit1). When extension card is installed, the number of the digital output terminals will increase according to the extension card. The maximum number of the digital output terminals is shown as follows.

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11