Chapter 4 Parameters

60Hz

30Hz 0V 0Hz

 

 

Pr.01.00=60Hz--Max. output Freq.

FWD

Potentiometer

 

 

Pr.04.00

=50.0%--Bias adjustment

 

 

Pr.04.01

=1--Negative bias

 

 

Pr.04.02

=200%--Input gain

5V 10V

 

Pr.04.03

=1--Negative bias: REV motion enabled

30Hz

REVGain:(10V/5V)*100%=200% 60Hz

Bias adjustment:((60Hz/60Hz)/(Gain/100%))*100%=200%

Example 8: Use negative slope

In this example, the use of negative slope is shown. Negative slopes are used in applications for control of pressure, temperature or flow. The sensor that is connected to the input generates a large signal (10V) at high pressure or flow. With negative slope settings, the AC motor drive will slow stop the motor. With these settings the AC motor drive will always run in only one direction (reverse). This can only be changed by exchanging 2 wires to the motor.

60Hz

negative slope

0Hz

0V10V

Pr.01.00=60Hz--Max. output Freq. Potentiometer

Pr.04.00 =100%--Bias adjustment Pr.04.01 =0--Positive bias Pr.04.02 =100%--Input gain

Pr.04.03 =1--Negative bias: REV motion enabled

Gain:(10V/10V)*100%=100%

Bias adjustment:((60Hz/60Hz)/(Gain/100%))*100%=100%

04.11

Minimum AVI Voltage

Unit: 0.1

 

Settings

0.0 to 10.0V

Factory Setting: 0.0

 

 

 

04.12

Minimum AVI Frequency (percentage of Pr.01.00)

Unit: 0.1

 

Settings

0.0 to 100.0%

Factory Setting: 0.0

 

 

 

04.13

Maximum AVI Voltage

Unit: 0.1

 

Settings

0.0 to 10.0V

Factory Setting: 10.0

 

 

 

04.14

Maximum AVI Frequency (percentage of Pr. 01.00)

Unit: 0.1

 

Settings

0.0 to 100.0%

Factory Setting: 100.0

 

 

 

04.15

Minimum ACI Current

Unit: 0.1

 

Settings

0.0 to 20.0mA

Factory Setting: 4.0

 

 

 

04.16

Minimum ACI Frequency (percentage of Pr. 01.00)

Unit: 0.1

 

Settings

0.0 to 100.0%

Factory Setting: 0.0

 

 

 

 