Delta Electronics VFD-E manual MI6=4 MI5=3 MI4=2 MI3=1, 04.09

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 133
Image 133

Chapter 4 Parameters

 

 

 

 

MI6=4

MI5=3

 

MI4=2

MI3=1

 

 

 

Master frequency

OFF

OFF

 

OFF

OFF

 

 

 

 

1st speed

OFF

OFF

 

OFF

ON

 

 

 

 

2nd speed

OFF

OFF

 

ON

OFF

 

 

 

 

3rd speed

OFF

OFF

 

ON

ON

 

 

 

 

4th speed

OFF

ON

 

OFF

OFF

 

 

 

 

5th speed

OFF

ON

 

OFF

ON

 

 

 

 

6th speed

OFF

ON

 

ON

OFF

 

 

 

 

7th speed

OFF

ON

 

ON

ON

 

 

 

 

8th speed

ON

OFF

 

OFF

OFF

 

 

 

 

9th speed

ON

OFF

 

OFF

ON

 

 

 

 

10th speed

ON

OFF

 

ON

OFF

 

 

 

 

11th speed

ON

OFF

 

ON

ON

 

 

 

 

12th speed

ON

ON

 

OFF

OFF

 

 

 

 

13th speed

ON

ON

 

OFF

ON

 

 

 

 

14th speed

ON

ON

 

ON

OFF

 

 

 

 

15th speed

ON

ON

 

ON

ON

 

 

 

 

 

 

 

 

 

 

 

04.09

Multi-function Input Contact Selection

 

 

 

Unit: 1

 

 

 

 

 

 

 

 

 

 

 

Settings

0 to 4095

 

 

 

 

Factory Setting: 0

 

 

 

 

 

 

 

 

 

 

This parameter can be used to set the status of multi-function terminals (MI1~MI6 (N.O./N.C.)

for standard AC motor drive).

The MI1~MI3 setting will be invalid when the operation command source is external terminal

(2/3wire).

Weights

 

 

 

 

 

 

0=N.O

Bit

5

4

3

2

1

0

1=N.C

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

The Setting method: It needs to convert binary number (6-bit) to decimal number for input.

For example: if setting MI3, MI5, MI6 to be N.C. and MI1, MI2, MI4 to be N.O. The setting

value Pr.04.09 should be bit5X25+bit4X24+bit2X22= 1X25+1X24+1X22= 32+16+4=52 as shown

in the following.

4-80

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 133
Image 133
Delta Electronics VFD-E manual MI6=4 MI5=3 MI4=2 MI3=1, 04.09