Chapter 4 Parameters

 

Settings

Function

Description

 

 

 

Parameter value 09 programs a Multi-function Input Terminals for

 

 

 

external Base Block control.

 

 

External Base

NOTE: When a Base-Block signal is received, the AC motor

9

Block

drive will block all output and the motor will free run. When

 

 

(Refer to Pr.08.06)

base block control is deactivated, the AC drive will start its

 

 

 

speed search function and synchronize with the motor

 

 

 

speed, and then accelerate to Master Frequency.

 

 

 

 

10

UP: Increase

Increase/decrease the Master Frequency each time an input is

Master Frequency

received or continuously when the input stays active. When both

 

 

 

 

 

inputs are active at the same time, the Master Frequency

 

 

DOWN: Decrease

11

increase/decrease is halted. Please refer to Pr.02.07, 02.08. This

 

Master Frequency

function is also called “motor potentiometer”.

 

 

 

 

 

 

 

 

 

 

 

 

Parameter value 12 programs one of the Multi-function Input

12

Counter Trigger

Terminals MI7 MI12 (Pr.11.06~Pr.11.11) to increment the AC

drive’s internal counter. When an input is received, the counter is

 

 

 

 

 

 

incremented by 1.

 

 

 

 

13

Counter Reset

When active, the counter is reset and inhibited. To enable

counting the input should be OFF. Refer to Pr.03.05 and 03.06.

 

 

 

 

 

 

 

 

 

 

Parameter value 14 programs one of the Multi-function Input

14

External Fault

Terminals MI7 MI12 (Pr.11.06~Pr.11.11) to be External Fault

 

 

 

(E.F.) inputs.

 

 

 

 

15

PID function

When an input ON with this setting is ON, the PID function will be

disabled

disabled.

 

 

 

 

 

 

 

 

 

AC motor drive will stop output and the motor free run if one of

16

Output Shutoff Stop

these settings is enabled. If the status of terminal is changed, AC

 

 

 

motor drive will restart from 0Hz.

 

 

 

 

17

Parameter lock

When this setting is enabled, all parameters will be locked and

enable

write parameters is disabled.

 

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11