Delta Electronics VFD-E Group 13 PG function Parameters for Extension Card, Ccw, 13.01, 13.02

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 202
Image 202

Chapter 4 Parameters

Group 13: PG function Parameters for Extension Card

Make sure that the extension card is installed on the AC motor drive correctly before using group 12 parameters. See Appendix B for details.

13.00PG Input

Factory Setting: 0

Settings

0

Disable PG

 

1

Single phase

 

2

Forward/Counterclockwise rotation

 

3

Reverse/Clockwise rotation

 

 

 

The relationship between the motor rotation and PG input is illustrated below:

FWD

REV

A phase leads B phase

A phase

CCW

B phase 13.00=2

 

 

B phase leads A phase

CW

A phase

B phase 13.00=3

 

PULSE

PG

GENERATOR

 

CW

A phase

B phase

 

13.01

PG Pulse Range

Unit: 1

 

Settings

1 to 20000

Factory Setting: 600

 

 

 

 

A Pulse Generator (PG) is used as a sensor that provides a feedback signal of the motor speed. This parameter defines the number of pulses for each cycle of the PG control.

13.02

Motor Pole Number (Motor 0)

Unit: 1

 

Settings

2 to 10

Factory Setting: 4

 

 

 

The pole number should be even (can’t be odd).

 

 

 

 

13.03

Proportional Gain (P)

Unit: 0.01

 

 

 

 

 

Settings

0.0 to 10.0

Factory Setting: 1.0

 

 

 

 

This parameter specifies proportional control and associated gain (P), and is used for speed control with PG feedback.

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-149

Page 202
Image 202
Delta Electronics VFD-E manual Group 13 PG function Parameters for Extension Card, Ccw, 13.01, 13.02, 13.03