Chapter 4 Parameters

This parameter sets the time for how long over-torque must be detected before “OL2” is displayed.

06.06Electronic Thermal Overload Relay Selection (OL1)

 

 

Factory Setting: 2

Settings

0

Operate with a Standard Motor (self-cooled by fan)

 

1

Operate with a Special Motor (forced external cooling)

 

2

Operation disabled

 

 

 

This function is used to protect the motor from overloading or overheating.

rated current of the motor%

100

80

60

40

20

25

50

100

150

 

rated frequency of the motor %

 

rated current of the motor%

100

80

60

40

20

25

50

100

150

 

rated frequency of the motor %

 

 

 

Standard motor

 

Special Motor

 

 

(self-cooled by fan)

(forced external cooling)

 

 

 

 

 

06.07

Electronic Thermal Characteristic

 

 

Unit: 1

 

Settings

30 to 600 sec

 

 

Factory Setting: 60

 

 

 

 

 

 

The parameter determines the time required for activating the I2t electronic thermal protection function. The graph below shows I2t curves for 150% output power for 1 minute.

Operation time (seconds)

350

 

 

 

 

 

 

 

300

 

 

 

 

 

 

 

 

 

 

50Hz or more

 

 

 

 

 

 

250

 

 

 

10Hz

 

 

 

200

 

 

 

5Hz

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

50

 

 

 

 

 

Load

 

 

 

 

 

 

0

50

100

150

200

250

factor (%)

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-93

Page 146