Chapter 4 Parameters

Group 11: Multi-function Input/Output Parameters for Extension Card

Make sure that the extension card is installed on the AC motor drive correctly before using group 11 parameters. See Appendix B for details.

11.00Multi-function Output Terminal MO2/RA2

11.01Multi-function Output Terminal MO3/RA3

11.02Multi-function Output Terminal MO4/RA4

11.03Multi-function Output Terminal MO5/RA5

11.04Multi-function Output Terminal MO6/RA6

11.05Multi-function Output Terminal MO7/RA7

 

Settings

0 to 21

Factory Setting: 0

 

 

 

Settings

Function

Description

0

No Function

 

 

 

 

 

1

AC Drive Operational

Active when the drive is ready or RUN command is “ON”.

 

 

 

2

Master Frequency

Active when the AC motor drive reaches the output

Attained

 

frequency setting.

 

 

 

 

 

 

3

Zero Speed

 

Active when Command Frequency is lower than the

 

Minimum Output Frequency.

 

 

 

 

 

 

 

4

Over-Torque Detection

Active as long as over-torque is detected. (Refer to Pr.06.03

~ Pr.06.05)

 

 

 

 

 

 

 

 

Baseblock (B.B.)

Active when the output of the AC motor drive is shut off

5

during baseblock. Base block can be forced by Multi-

Indication

 

 

 

function input (setting 09).

 

 

 

 

 

 

6

Low-Voltage Indication

Active when low voltage (Lv) is detected.

 

 

 

7

Operation Mode

Active when operation command is controlled by external

Indication

 

terminal.

 

 

 

 

 

 

8

Fault Indication

Active when a fault occurs (oc, ov, oH, oL, oL1, EF, cF3,

HPF, ocA, ocd, ocn, GFF).

 

 

 

 

 

 

 