Appendix B Accessories

B.5 Zero Phase Reactor (RF220X00A)

Dimensions are in millimeter and (inch)

Cable

Recommended Wire

 

 

 

Size

 

 

Wiring

type

 

 

 

Qty.

(Note)

 

2

Nominal

 

Method

 

AWG

mm

(mm2)

 

 

 

10

5.3

5.5

1

Diagram

Single-

A

 

 

 

 

core

 

 

 

 

 

2

33.6

38

4

Diagram

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

12

3.3

3.5

1

Diagram

Three-

A

 

 

 

 

 

 

 

 

 

core

1

42.4

50

4

Diagram

 

 

B

 

 

 

 

 

 

 

 

 

 

 

Note: 600V Insulated unshielded Cable.

Diagram A

Please wind each wire 4 times around the core. The reactor must be put at inverter output as close as possible.

 

 

 

Zero Phase Reactor

 

 

 

 

Power

R/L1

U/T1

 

S/L2

V/T2

MOTOR

Supply

T/L3

W/T3

 

 

 

 

 

 

 

Diagram B

Please put all wires through 4 cores in series without winding.

 

 

 

Zero Phase Reactor

Power

R/L1

U/T1

MOTOR

Supply

S/L2

V/T2

T/L3

W/T3

 

 

 

 

 

Note 1: The table above gives approximate wire size for the zero phase reactors but the selection is ultimately governed by the type and diameter of cable fitted i.e. the cable must fit through the center hole of zero phase reactors.

Note 2: Only the phase conductors should pass through, not the earth core or screen.

Note 3: When long motor output cables are used an output zero phase reactor may be required to reduce radiated emissions from the cable.

B-14

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 251
Image 251
Delta Electronics VFD-E manual Zero Phase Reactor RF220X00A, Awg, Diagram a, Diagram B