Delta Electronics VFD-E manual 03.05, 03.06

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 117
Image 117

Chapter 4 Parameters

For Example: When using the meter with full scale of 5 volts, adjust Pr.03.04 to 50%. If Pr.03.03 is set to 0, then 5VDC will correspond to Maximum Output Frequency.

03.05

Terminal Count Value

Unit: 1

 

 

 

 

 

Settings

0 to 9999

Factory Setting: 0

This parameter sets the count value of the internal counter. To increase the internal counter, one of Pr.04.05 to 04.08 should be set to 12. Upon completion of counting, the specified output terminal will be activated. (Pr.03.00 to Pr.03.01 set to 10).

When the display shows c555, the drive has counted 555 times. If display shows c555, it means that real counter value is between 5,550 and 5,559.

03.06

Preliminary Count Value

Unit: 1

 

Settings

0 to 9999

Factory Setting: 0

 

 

 

 

When the counter value reaches this value, the corresponding multi-function output terminal will be activated, provided one of Pr.03.00 to Pr.03.01 set to 11 (Preliminary Count Value Setting). This multi-function output terminal will be deactivated upon completion of Terminal Count Value Attained.

The timing diagram:

 

 

 

2msec

 

 

 

Display

 

 

 

 

 

 

 

(Pr.00.04=1)

 

 

 

 

TRG

 

 

 

 

Counter Trigger

 

 

 

 

2msec

The width of trigger signal

Preliminary Count Value

should not be less than

(Pr. 03.00~Pr. 03.01=11) Ex:03.05=5,03.06=3

2ms(<250 Hz)

Terminal Count Value (Pr. 03.00~Pr. 03.01=10)

03.07EF Active when Terminal Count Value Attained

 

 

Factory Setting: 0

Settings

0

Terminal count value attained, no EF display

 

1

Terminal count value attained, EF active

 

 

 

If this parameter is set to 1 and the desired value of counter is attained, the AC drive will treat it as a fault. The drive will stop and show the “EF” message on the display.

4-64

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 117
Image 117
Delta Electronics VFD-E manual 03.05, 03.06