Delta Electronics VFD-E manual How to Control by CANopen, Stop

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 362
Image 362

Appendix D How to Use PLC Function

Index

Sub

Definition

Factory

RW

Size

Unit

Map

NOTE

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 : disable drive function

 

 

 

 

 

 

 

 

1 :slow down on slow down

 

 

 

 

 

 

 

 

ramp

 

 

 

 

 

 

 

 

2: slow down on quick stop

0x605A

0

Quick stop option

2

RW

S16

1ms

Yes

ramp (2th decel. time)

5 slow down on slow down

code

 

 

 

 

 

 

 

ramp and stay in QUICK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STOP

 

 

 

 

 

 

 

 

6 slow down on quick stop

 

 

 

 

 

 

 

 

ramp and stay in QUICK

 

 

 

 

 

 

 

 

STOP

0x6060

0

Mode of

2

RO

U8

 

Yes

Speed mode

operation

 

 

 

 

 

 

 

 

 

0x6061

0

Mode of

2

RO

U8

 

Yes

 

operation display

 

 

 

 

 

 

 

 

 

 

E.2 How to Control by CANopen

To control the AC motor drive by CANopen, please set parameters by the following steps: Step 1. Operation source setting: set Pr.02.01 to 5 (CANopen communication. Keypad STOP/RESET disabled.)

Step 2. Frequency source setting: set Pr.02.00 to 5 (CANopen communication)

Step 3. CANopen station setting: set Pr.09.13 (CANopen Communication Address 1-127)

Step 4. CANopen baud rate setting: set Pr.09.14 (CANBUS Baud Rate)

Step 5. Set multiple input function to quick stop when necessary: Set Pr.04.05 to 04.08 or Pr.11.06 to 11.11 to 23.

According to DSP-402 motion control rule, CANopen provides speed control mode. There are many status can be switched during Start to Quick Stop. To get current status, please read “Status Word”. Status is switched by the PDO index control word via external terminals.

Control word is a 16-byte in index 0x6040 and each bit has specific definition. The status bits are bit

4 to bit 6 as shown in the following: Bit 4: ramp function enabled

Bit 5: ramp function disabled

Bit 6: rfg use reference

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

E-13