Chapter 4 Parameters

08.12

Skip Frequency 2 Lower Limit

Unit: 0.01

08.13

Skip Frequency 3 Upper Limit

Unit: 0.01

08.14

Skip Frequency 3 Lower Limit

Unit: 0.01

 

Settings

0.00 to 600.0Hz

Factory Setting: 0.00

 

 

 

 

These parameters set the Skip Frequencies. It will cause the AC motor drive never to remain within these frequency ranges with continuous frequency output.

These six parameters should be set as follows Pr.08.09 Pr.08.10 Pr.08.11 Pr.08.12

Pr.08.13 Pr.08.14.

 

 

 

The frequency ranges may be overlapping.

 

 

command

08.09

 

 

 

 

 

 

 

 

08.10

 

 

 

frequency

08.11

 

 

 

08.12

 

 

 

 

 

 

 

 

08.13

 

 

 

internal

08.14

 

 

 

0

setting frequency

 

 

 

 

 

 

 

 

08.15 Auto Restart After Fault

 

Unit: 1

Settings

0 to 10

 

Factory Setting: 0

 

0

Disable

 

 

Only after an over-current OC or over-voltage OV fault occurs, the AC motor drive can be reset/restarted automatically up to 10 times.

Setting this parameter to 0 will disable automatic reset/restart operation after any fault has occurred.

When enabled, the AC motor drive will restart with speed search, which starts at the frequency before the fault. To set the waiting time before restart after a fault, please set Pr. 08.07 Base Block Time for Speed Search.

08.16

Auto Reset Time at Restart after Fault

Unit: 0.1

 

Settings

0.1 to 6000 sec

Factory Setting: 60.0

 

 

 

 