Chapter 4 Parameters

Content

Address

 

Function

 

 

 

 

 

 

Bit 10

1: Operation command controlled by

 

 

communication interface

 

 

 

 

 

 

 

 

 

Bit 11-15

Reserved

 

 

 

 

 

2102H

Frequency command (F)

 

 

 

 

2103H

Output frequency (H)

 

 

 

 

2104H

Output current (AXXX.X)

 

 

 

 

 

2105H

Reserved

 

 

 

 

 

 

2106H

Reserved

 

 

 

 

 

 

2107H

Reserved

 

 

 

 

 

2108H

DC-BUS Voltage (UXXX.X)

 

 

 

 

2109H

Output voltage (EXXX.X)

 

 

 

 

210AH

Display temperature of IGBT (°C)

 

 

 

 

2116H

User defined (Low word)

 

 

 

 

2117H

User defined (High word)

 

 

 

 

Note: 2116H is number display of Pr.00.04. High byte of 2117H is number of decimal places of 2116H. Low byte of 2117H is ASCII code of alphabet display of Pr.00.04.

3.6 Exception response:

The AC motor drive is expected to return a normal response after receiving command messages from the master device. The following depicts the conditions when no normal response is replied to the master device.

The AC motor drive does not receive the messages due to a communication error; thus, the AC motor drive has no response. The master device will eventually process a timeout condition.

The AC motor drive receives the messages without a communication error, but cannot handle them. An exception response will be returned to the master device and an error message “CExx” will be displayed on the keypad of AC motor drive. The xx of “CExx” is a decimal code equal to the exception code that is described below.

In the exception response, the most significant bit of the original command code is set to 1, and an exception code which explains the condition that caused the exception is returned.

Example of an exception response of command code 06H and exception code 02H:

ASCII mode:

RTU mode:

4-126

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 179
Image 179
Delta Electronics VFD-E manual Ascii mode RTU mode