Chapter 4 Parameters

For standard AC motor drive (without extension card), the multi-function input terminals are MI1 to MI6 as shown in the following.

Weights Bit

0=set internal terminal to be OFF 1=set internal terminal to be ON

54 3 2 1 0 MI1

MI2 MI3 MI4 MI5 MI6

For example, if setting MI3, MI5 and MI6 to be ON, Pr.04.28 should be set to

bit5X25+bit4X24+bit2X22= 1X25+1X24+1X22= 32+16+4=52 as shown in the following.

Weights

 

 

 

 

 

 

0=OFF

 

 

 

 

 

 

1=ON

Bit

1

1

0

1

0

0

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

When extension card is installed, the number of the multi-function input terminals will increase according to the extension card. The maximum number of the multi-function input terminals is shown as follows.

Weights Bit

0=set internal terminal to be OFF 1=set internal terminal to be ON

11 10 9 8 7 6 5 4 3 2 1 0 MI1

MI2

MI3

MI4

MI5

MI6

MI7

MI8

MI9

MI10

MI11

MI12

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-87

Page 140
Image 140
Delta Electronics VFD-E manual =Off