Chapter 4 Parameters

00.04

Content of Multi-function Display

 

6

Display the power factor angle in º of terminals U/T1,

 

V/T2, W/T3 to the motor

 

 

 

7

Display the output power in kW of terminals U, V and W

 

to the motor.

 

 

 

8

Display the estimated value of torque in Nm as it relates

 

to current.

 

 

 

9

Display the signal of AVI analog input terminal (V).

 

 

 

10

Display the signal of ACI analog input terminal (mA)or

 

display the signal of AVI2 analog input terminal-(V).

 

 

 

11 Display the temperature of IGBT (h) in °C

12 Display AVI3/ACI2 level (I.)

13 Display AVI4/ACI3 level (i.)

14 Display PG speed in RPM (G)

15 Display motor number (M)

When Pr00.03 is set to 03, the display is according to the setting of Pr00.04.

 

00.05

User Defined Coefficient K

Unit: 0. 1

 

 

Settings

0. 1 to d 160.0

Factory Setting: 1.0

 

 

 

The coefficient K determines the multiplying factor for the user-defined unit.

 

The display value is calculated as follows:

 

 

U (User-defined unit) = Actual output frequency * K (Pr.00.05)

 

 

Example:

 

 

 

A conveyor belt runs at 13.6m/s at motor speed 60Hz.

 

 

K = 13.6/60 = 0.22

(0.226667 rounded to 1 decimal), therefore Pr.00.05=0.2

With Frequency command 35Hz, display shows U and 35*0.2=7.0m/s. (To increase accuracy, use K=2.2 or K=22.7 and disregard decimal point.)

00.06Power Board Software Version

Settings

Read Only

Display

#.##

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-39