Delta Electronics VFD-E manual Device Reference Table, MI1 MI2 MI3 MI4 MI5 MI6, MI7 MI8 MI9

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 286
Image 286

NOTE

Appendix D How to Use PLC Function

When power on after power off, the PLC status will be in “PLC1”.

4.When you are in “PLC2”, please remember to change to “PLC1” when finished to prevent anyone modifying PLC program.

NOTE

When output/input terminals (MI1~MI9, Relay1~Relay 4, MO1~MO4) are used in PLC program, they cannot be used in other places. For example, When Y0 in PLC program is activated, the corresponding output terminals Relay (RA/RB/RC) will be used. At this moment, parameter 03.00 setting will be invalid. Because the terminal has been used by PLC.

NOTE

The PLC corresponding input points for MI1 to MI6 are X0 to X5. When extension card are added, the extension input points will be numbered from X06 and output points will start from Y2 as shown in chapter D.2.2.

D.2.2 Device Reference Table

 

Device

 

 

 

 

X

 

 

 

 

 

 

ID

0

1

2

3

4

5

6

7

10

 

 

Terminals of AC

MI1

MI2

MI3

MI4

MI5

MI6

--

--

--

 

 

Drives

 

 

 

 

 

 

 

 

 

 

 

 

 

3IN/3OUT Card

--

--

--

--

--

--

MI7

MI8

MI9

 

(EME-D33A)

 

 

 

 

 

 

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

D-3

Page 286
Image 286
Delta Electronics VFD-E manual Device Reference Table, MI1 MI2 MI3 MI4 MI5 MI6, MI7 MI8 MI9