Chapter 4 Parameters

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

6: 8,N,1 (Modbus, RTU)

 

 

 

 

7: 8,E,2 (Modbus, RTU)

 

 

09.09

Communication

8: 8,O,2 (Modbus, RTU)

 

 

Protocol for USB

9: 7,N,1 (Modbus, ASCII)

 

 

 

Card

 

 

 

10: 7,E,2 (Modbus, ASCII)

 

 

 

 

 

 

 

 

11: 7,O,2 (Modbus, ASCII)

 

 

 

 

 

 

 

 

Transmission Fault

0: Warn and keep operating

 

 

 

1: Warn and ramp to stop

 

 

09.10

Treatment for USB

0

 

2: Warn and coast to stop

 

 

Card

 

 

 

3: No warning and keep operating

 

 

 

 

 

 

 

 

 

 

 

09.11

Time-out Detection

0.1 ~ 120.0 seconds

0.0

 

for USB Card

0.0: Disable

 

 

 

 

 

 

 

 

 

 

COM port for PLC

0: RS485

 

 

09.12

Communication

1: USB card

0

 

(NOT for VFD*E*C

 

 

 

 

 

 

 

 

models)

 

 

 

 

 

 

 

 

Group 10 PID Control Parameters

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

 

 

 

Setting

 

 

 

0: Disable PID operation

 

 

 

 

1: Keypad (based on Pr.02.00)

 

 

10.00

PID Set Point

2: 0 to +10V from AVI

0

 

Selection

 

 

 

3: 4 to 20mA from ACI or 0 to +10V from

 

 

 

 

 

 

 

 

AVI2

 

 

 

 

4: PID set point (Pr.10.11)

 

 

 

 

 

 

 

 

 

0: Positive PID feedback from external

 

 

 

 

terminal AVI (0 ~ +10VDC)

 

 

 

 

1: Negative PID feedback from external

 

 

 

 

terminal AVI (0 ~ +10VDC)

 

 

10.01

Input Terminal for

2: Positive PID feedback from external

0

 

PID Feedback

terminal ACI (4 ~ 20mA)/ AVI2 (0 ~

 

 

 

 

 

 

+10VDC).

 

 

 

 

3: Negative PID feedback from external

 

 

 

 

terminal ACI (4 ~ 20mA)/ AVI2 (0 ~

 

 

 

 

+10VDC).

 

 

 

 

 

 

 