Note- See the procedure for system-stopped maintenance for inactive/cold maintenance in a
single-chassisco nfiguration.
Note- Use the DR of the system board on a physical partition for active/cold maintenance.
Forthe XCP an d Oracle VM Server for SPARC/SRU versions that correspond to the DR, see
thelatest Produc t Notes.
Note- Active/co ld maintenance can be performed only for a building block configuration.
Note- In the case of a d ual power feed, connect the power cords in their original positions by
referringto th ere cord that you made before the start of maintenance.
XSCF> diagxbu -y -b 00 -p 02
XSCF> showlogs error
Active/Cold maintenance
Inactive/Cold maintenance
System-stopped maintenance
7.6.1 Active/Cold maintenance
1. Connect all the power cords to the PSU backplane unit of the chassis
requiringmaintenance.
For details, see "6.5.1 Installing the power cord."
2. Returnto the operation of theXSCF firmware replacefru command to confirm
thatthe chassis has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
3. Executethe diagxbu command to diagnose the crossbar cables.
Diagnosis is performed when the system board of the chassis connected with the
crossbar cables is incorporated into the physical partition, and the physical
partitionis powered on.
Theex ample below specifies the following:
00:BB-ID ofthe c hassis to start the diagnosis
02: PPAR-ID of the destination where the chassis to start the diagnosis is
connected (You can specify only one of these.)
4. Executethe showlogs command to confirm that the system is operating
normally.
FujitsuM10-4/Fujitsu M10-4S/SPARC M10-4/SPARC M10-4S Service Manual December 2013148