11.2.2 Remedies for alarms

11. TROUBLESHOOTING

11.2.2 Remedies for alarms

When any alarm has occurred, eliminate its cause, ensure safety, then reset the

CAUTION alarm, and restart operation. Otherwise, injury may occur.

If an absolute position erase alarm (AL.25) occurred, always make home position setting again. Otherwise, misoperation may occur.

POINT

When any of the following alarms has occurred, always remove its cause and allow about 30 minutes for cooling before resuming operation. If operation is resumed by switching control circuit power off, then on to reset the alarm, the servo amplifier and servo motor may become faulty.

Regenerative error (AL.30) Overload 1 (AL.50) Overload 2 (AL.51)

The alarm can be deactivated by switching power off, then on press the "SET" button on the current alarm screen or by turning on the reset (RES). For details, refer to Section 11.2.1.

When an alarm occurs, the trouble (ALM) switches off and the dynamic brake is operated to stop the servo motor. At this time, the display indicates the alarm No.

The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The optional servo configuration software may be used to refer to the cause.

Display

Name

Definition

 

 

Cause

Action

AL.10

Undervoltage

Power supply

1. Power supply voltage is low.

Review the power supply.

 

 

voltage dropped.

2. There was an instantaneous

 

 

 

MR-J2S- CL:

 

control power failure of 60ms or

 

 

 

160VAC or less

 

longer.

 

 

 

MR-J2S- CL1:

3. Shortage of power supply capacity

 

 

 

83VAC or less

 

caused the power supply voltage to

 

 

 

 

 

drop at start, etc.

 

 

 

 

4. Power was restored after the bus

 

 

 

 

 

voltage had dropped to 200VDC.

 

 

 

 

 

(Main circuit power switched on

 

 

 

 

 

within 5s after it had switched off.)

 

 

 

 

5. Faulty parts in the servo amplifier

Change the servo amplifier.

 

 

 

 

 

Checking method

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm (AL.10) occurs if power is

 

 

 

 

 

 

switched on after disconnection

 

 

 

 

 

 

of all cables but the control

 

 

 

 

 

 

circuit power supply cables.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL.12

Memory error 1

RAM, memory fault

Faulty parts in the servo amplifier

Change the servo amplifier.

AL.13

Clock error

Printed board fault

 

 

Checking method

 

 

 

 

 

 

 

 

 

 

 

Alarm (any of AL.11 and 13)

 

 

 

 

 

 

occurs if power is switched on

 

 

 

 

 

 

after disconnection of all cables

 

 

 

 

 

 

but the control circuit power

 

 

 

 

 

 

supply cables.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL.15

Memory error 2

EEP-ROM fault

1. Faulty parts in the servo amplifier

Change the servo amplifier.

 

 

 

 

 

Checking method

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm (AL.15)

 

 

 

 

 

 

occurs if power is switched on

 

 

 

 

 

 

after disconnection of all cables

 

 

 

 

 

 

but the control circuit power

 

 

 

 

 

 

supply cables.

 

 

 

 

 

 

 

 

 

 

 

2.The number of write times to EEP- ROM exceeded 100,000.

AL.16

Encoder error 1

Communication

1.

Encode connector (CN2)

Connect correctly.

 

 

error occurred

 

disconnected.

 

 

 

between encoder

2.

Encoder fault

Change the servo motor.

 

 

and servo amplifier.

3.

Encoder cable faulty

Repair or change the cable.

 

 

 

 

(wire breakage or short)

 