(2)Startup procedure

4. OPERATION

(2)Startup procedure

(a)Power on

1)Switch off the servo-on (SON).

2)When main circuit power/control circuit power is switched on, "PoS" (Current position) appears on the servo amplifier display.

In the absolute position detection system, first power-on results in the absolute position lost (AL.25) alarm and the servo system cannot be switched on. This is not a failure and takes place due to the uncharged capacitor in the encoder.

The alarm can be deactivated by keeping power on for a few minutes in the alarm status and then switching power off once and on again.

Also in the absolute position detection system, if power is switched on at the servo motor speed of 500r/min or higher, position mismatch may occur due to external force or the like. Power must therefore be switched on when the servo motor is at a stop.

(b)Test operation

Using jog operation in the "test operation mode" of the Servo Configuration Software, make sure that the servo motor operates. (Refer to Section 6.7.1, 7.8.2)

(c)Parameter setting

Set the parameters according to the structure and specifications of the machine. Refer to Chapter 5 for the parameter definitions and to Sections 6.4 and 7.6 for the setting method.

Parameter

Name

Setting

 

Description

 

 

20

 

 

 

 

No.0

Command system, regenerative

 

 

 

 

 

 

 

Absolute value command system.

 

 

 

 

 

 

 

brake option selection

 

 

 

 

 

 

 

MR-RB032 regenerative brake option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is used.

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

When forward rotation start (ST1) is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valid, address is incremented in CCW

No.1

Feeding function selection

 

 

 

 

 

 

 

direction.

 

 

 

 

 

 

 

 

 

Since command resolution is 10 times,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

feed length multiplication factor of 10

 

 

 

 

 

 

 

 

 

times is selected.

 

 

 

 

 

 

 

 

 

No.2

Function selection 1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Absolute position detection system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.4

Electronic gear numerator (CMX)

8192

 

From calculation result of formula (4.1)

No.5

Electronic gear denominator (CDV)

5000

 

From calculation result of formula (4.1)

After setting the above parameters, switch power off once. Then switch power on again to make the set parameter values valid.

(d)Program setting

Set the program according to the operation pattern. Refer to Section 4.2 for the program definitions and to Sections 4.2 and 6.5 for the setting method.

Program

 

Description

SPN (2500)

Speed (Motor speed)

2500 [r/min]

STA (200)

Acceleration time constant

200 [ms]

STB (300)

Deceleration time constant

300 [ms]

MOV (20000)

Absolute move command

20000 [ 10STM m]

STOP

Program end

 

(e)Servo-on

Switch the servo-on in the following procedure:

1)Switch on main circuit/control circuit power.

2)Switch on the servo-on (SON).

When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is locked. By using the sequence in the diagnostic mode in Section 7.3, the ready status can be shown on the servo amplifier display. In the operation-ready status, the following screen appears.