4 Monitoring Functions

4.6

Listing of the alarms/alarm description

Alarm No.

3007

 

 

Alarm Text:

ºWrong setting data programº

 

 

 

Reason:

±

G25/G26 has been programmed

 

±

G92 has been programmed with an address other than ºSº or ºPº

Remedy:

±

M19 has been programmed with an address other than ºSº

As for alarm 3000

 

 

Alarm No.

3008

 

 

Alarm Text:

ºSubroutine errorº

 

 

 

Reason:

±

Subroutine call without pass count ºPº

 

±

M30 has been programmed as end of program

 

±

M17 missing at end of program

 

±

5 levels of nesting have been called

 

±

M17 has been programmed in a main program

Remedy:

As for alarm 3000

 

 

Alarm No.

3009

 

 

Alarm Text:

ºProgram disabledº

 

 

 

Explanation:

±

L0 preselected in the AUTOMATIC display (not permitted).

 

±

Missing program called by PLC.

 

 

Alarm No.

3010

 

 

Alarm Text:

ºIntersection errorº

 

 

Reason:

This error can appear in conjunction with the L95 stock removal cycle,

 

when:

 

±

A contouring program has been programmed without G00, G01,

 

 

G02, G03

 

±

@ 714 has been programmed in a contouring program

 

±

An incorrect plane has been selected in a contouring program

 

±

No intersection point has been found

 

±

More than a quarter circle has been programmed in a contouring

 

 

program

Remedy:

As for alarm 3000

 

 

Alarm No.

3011

 

 

Alarm Text:

ºToo many axes/axes twiceº

 

 

 

Reason:

±

An axis has been programmed twice in the same block

 

±

More axes have been programmed than present on the machine

Remedy:

As for alarm 3000

 

 

 