When the SOFT STOP AMPS THRE S H OLD is being applied, a sta tus message
‘‘SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING’’ is shown.
Chilled Water Recycle Mode
The machine may cycle off and wait until the load incr eas e s to restart again when t he
compressor is running in a lightly loaded condi ti on. This cycling of the ch ill er is normal and is
known as recycle. A recycle shutdown is initiated when any of the following conditions are true:
when in LCW control, the dif ference between the
LEAVING CHILLED WATER
tem-
perature and
ENTERING CHILLED W ATER
temperature i s less than the
RECYCLE
SHUTDOWN DELTA T
(found in the SERVICE 1 t able) and the
LEAVING CHILLED
WATER TEMP
is below the
CONTROL POINT
, and the
CONTROL POINT
has not
increased in the last 5 minu tes
when
ECW CONTROL OPTION
is enabled, the differ en ce between the
ENTERING
CHILLED WATER
temperature and the
LEAVING CHILLED WATER
temperature is
less than the
RECYCLE SHUTDOWN DEL TA T
(found in the SERVICE 1 ta ble ) and
the
ENTERING CHILLED WATER TEMPERATURE
is below the
CONTROL POINT
,
and the
CONTROL PO INT
has not increased in the last 5 minutes
when the
LEAVING CHILLED WATER
temperature is wit hin 3° F (2° C) of the
BRINE
REFRIG TRIPPOINT
When the machine is in RECYCLE mode, the chil led water pump relay r emains energized so
that the chilled water temperature can be monitored for increasing load. The recycle control
uses
RECYCLE RESTART DELT A T
to check when the compressor should be restarted. This