Table 8 — LID Primary and Secondary Messages and Custom Alarm/Aler t Messages
with Troubleshooting Guides
H. Normal Run with Reset, Temperature, Or Demand
Primary Message Secondary Messa ge Probable Cause/ Remedy
Running — Reset Active 4-20MA Signal
Reset program active base d upon Config
table setup.
Running — Reset Active Remote Sensor Control
Running — Reset Active CHW Temp Difference
Running — Temp Control Leaving Chilled Water Default method of t emperature control.
Running — Temp Control Entering Chilled Water ECW control activated on Config table.
Running — Temp Control Temperature Ramp Loading Ramp loading in effect . Use Service1 table to
modify.
Running — Demand Limit ed By Demand Ramp Loading Ramp loading in effect . Use Service1 table to
modify.
Running — Demand Limit ed By Local Demand Setpoint Demand limit setpoint is < actual demand.
Running — Demand Limit ed By 4-20MA Signal
Demand limit is active based on Config ta ble
setup.
Running — Demand Limit ed By CCN Signal
Running — Demand Limit ed By Loadshed/Redline
Running — Temp Control Hot Gas Bypass Hot Gas Bypass is energized. See surg e pre-
vention in the Control section.
Running — Demand Limit ed By Local Signal Active demand limit manua lly overridden or
Status01 table.
Running — Temp Control Ice Build Mode Machine is running under Ice Build tempera-
ture control.