Default Screen Fr eez e
Whenever an alarm occurs, the LID default screen will freeze displaying the condition of the
machine at the time of alarm . Knowledge of the operat ing state of the chiller at th e time an
alarm occurs is useful when t roubleshooting. C urrent machine i nformation can be viewed on the
Status tables. Once all existing alarms are cleared (by pressing the RESET softkey), the default
LID will return to norma l operation.
Motor Cooling Control (H e rmetic Motors Only)
Motor temperature is re duc e d by refrigerant enteri ng the motor shell and evap orating. The
refrigerant is regula ted by the motor cool ing relay. This relay wi ll energize when the compressor
is running and motor tempe rature is above 125 F (51 .7 C). The relay will close when motor
temperature is below 100 F (37 .8 C). Note t hat there is a lways a minimu m flow of refri gerant
when the compressor is ope rating for motor coolin g; the relay only control s additional
refrigerant to the motor.
Note: An additional motor cooling relay is not required for Hermetic FA style compressors.
Auxiliary Oil Pump Control (Open Drive Machines Only)
The auxiliary oil pump ( optional) is contr olled by the PIC. During start-up, if the main oi l pump
cannot raise pressure t o 18 psid (124 kPa), the aux ili ary oil pump will be energ ized. During
compressor operation , the auxiliary oil pump will be energized if the oil pressu r e fa lls below the