Check Starter
Use the instructio n and service manua l supplied by the st arter manufacture r to verify that t he
starter has been installed correctly.
Whenever a starter safet y trip device activates, wa it at lea st 30 seconds before res et ting the
safety. The microproc e ssor maintains its out pu t to the 1CR relay for 10 seco nds after starter
safety shutdown to det er m in e the fault mode of fail ur e.
CAUTION CAUTION
!
BE AWARE that certain au t o matic start arrangem en ts
can engage the starter
.
Open the disconnect
ahead
of the starter in addition to shutting off the machine
or pump.
CAUTION CAUTION
!
The main disconnect on th e starter front panel may n ot deenergize all int ern al
circuits. Open all internal and remote disconnects before servicing the starter.