* [LIMIT] is shown on the LID as the temperature, pre ssu re, voltage, etc., set po int predefined or select ed
by the operator as an over r ide , alert, or alarm contit ion. [VALUE] is the actual temperature, press ur e,
voltage, etc., at which t he control tripped.
Recycle Alert
Excessive Recycle
Starts Excessive recycle
starts. The machine load is t oo small to keep the
machine on line and there have been
more than 5 restarts in 4 hours. Increase
machine load, adjust hot ga s bypass,
increase RECYCLE RESTART DELTA T.
Table 8 — LID P rimary and Se condary Mes sages and Cust om Alarm/A le rt Messages
with Troubleshooting Guides
L. Machine Alerts (Continued)
Primary
Message Secondary
Message Alarm Message/
Primary Cause Additional Cause/R emedy