Table 8 — LID Primary and Secondary Messages and Custom Alarm/A lert Me ss ages
with Troubleshooting Guides
J. Out-of-Range Sensor Failures
Primary Message Secondary Messa ge Alarm Message/Primary
Cause Additional Cause/
Remedy
Sensor Fault Leaving CHW Tempera-
ture Sensor Fault: Check l eaving CHW
sensor.
See
sensor test procedure
and check sensors for
proper operation and
wiring.
Sensor Fault Entering CHW Tempera-
ture Sensor Fault: Check en tering
CHW sensor.
Sensor Fault Condenser Pressure Sensor Fault: Check con denser
pressure transducer.
Sensor Fault Evaporator Pressure Sensor Fault: Check eva porator
pressure transducer.
Sensor Fault Bearing Temperature Sensor Fault: Check be aring tem-
perature sensor.
Sensor Fault Motor Winding Temp Sensor Fault: Check motor tem-
perature sensor.
Sensor Fault Discharge Temperature Sensor Fault: Check disc harge
temperature sensor.
Sensor Fault Oil Sump Temperature Sensor Fault: Check oil sump tem-
perature sensor.
Sensor Fault Oil Pressure Transducer Sensor Fault: Check oi l pressure
transducer.