Note: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded,
tinned copper. I ndividual condu ctors must be i nsulated with P VC, PVC/nylon, vinyl,
Teflon, or polyethyle ne. An aluminum/polye ster 100% foil shield an d an ou ter jacket of
PVC, PVC/nylon, c hrome vinyl or Tefl on with a minimum o perating temperatu re range of
–20 C to 60 C is required. See t abl e below for cables that me et the requirements.
When connecting the CCN communication bus to a system element, a color code system for
the entire network is reco mmended to simplify ins t allation and checkout . The following color
code is recommended:
Manufacturer Cable No.
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
SIGNAL TYPE CCN BUS CONDUCTOR
INSULATION COLOR PSIO MODULE COMM 1
PLUG (J5) PIN NO.
+
Ground
RED
WHITE
BLACK
1
2
3