CONFIG TABLECONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA –30 to 30
(–17 to 17) DEG F
(DEG C) 10
(6)
RESET TYPE 2
Remote Temp(No Reset) –40to 245
(–40 to 118) DEG F
(DEC C) 85
(29)
Remote Temp(Full Reset) –40 to 245
(–40 to 118) DEG F
(DEG C) 65
(18)
Degrees Reset –30 to 30
(–17 to 17) DEG F
(DEG C) 10
(6)
RESET TYPE 3
CHW Temp(No Reset) 0to15
(0 to 8) DEG F
(DEG C) 10
(6)
CHW Temp(Full Reset) 0to15
(0 to 8) DEG F
(DEG C) 0
(0)
Degrees Reset –30 to 30
(–17 to 17) DEG F
(DEG C) 5
(3)
Select/Enable Reset Type 0to3 0
ECW Control Option Disable/Enable Disable
Demand Limit at 20 mA 40 to 100 % 40
20 mA Demand Limit Option Disable/Enable Disable
Auto Restart Option Disable/Enable Disable
Remote Contacts Option Disable/Enable Disable
TempPulldown Deg/Min 2to10 3
Load Pulldown %/Min 5to20 10
Select Ramp Type:
Temp=0/Load=1 0/1 1
Loadshed Group Number 0to99 0
Loadshed Demand Delta 0to60 % 20
Maximum Loadshed Time 0 to 120 Min 60
CCN Occupancy Config:
Schedule Number 3to99 3
CCN Occupancy Config:
Broadcast Option Disable/Enable Disable
ICE BUILD Option Disable/Enable Disable
ICE BUILD TERMINATION:
0 =Temp,1 =Contacts, 2 =Both 0,1, 2 0
ICE BUILD RECYCLE Option Disable/Enable Disable
CL-5