Note: This screen provides th e m ean s to generate alert messag es based on exceeding t he ‘‘ Temp’’ thresh-

old for each poi nt listed. If the ‘ ‘Enable’’ is set to 1, a value abo ve the ‘‘Temp’’ thr eshold shall gen erate

an alert message. If the ‘‘ Enable’’ is set to 2, a valu e bel ow the ‘‘Temp Alert’’ thre shold shall generate

an alert message. If the ‘‘ Enable’’ is set to 0, aler t ge neration is disabled. If th e “Enable” is set to 3, a

value above the “Temp” th reshold will generate an ala rm. If the “Enable” is set t o 4, a value below the

“Temp” threshold will ge nerate an alarm.

OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE 1 20 m A Power So urce
SPARE 2 20 m A Power So urce
SPARE ALERT ENABLE
Disable = 0, 1 = High Ale rt, 2 = Low Alert,
3 = High Alarm, 4 = Low Ala rm
Temp = Alert Threshold
Spare Temp 4 Enable
Spare Temp 4 Alert
Spare Temp 5 Enable
Spare T emp 5 Alert
Spare Temp 6 Enable
Spare Temp 6 Alert
Spare Temp 7 Enable
Spare T emp 7 Alert
Spare Temp 8 Enable
Spare Temp 8 Alert
Spare Temp 9 Enable
Spare T emp 9 Alert
0, 1
0, 1
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–0-118)
0-4
–40-245 (–40-118)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
sp1 20 ma
sp2 20 ma
spr4 en
spr4 al
spr5 en
spr5 al
spr6 en
spr6 al
spr7 en
spr7 al
spr8 en
spr8 al
spr9 en
spr9 al
0
0
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
Table 2, Example 8 — Service2 Display Screen (Continued)

Description Configurable

Range Units Reference

Point

Name

Default

Value