b. Valve positions: Close valves 3 and 4, open valves 2 an d 5.
c. Turn on pumpout conden s er wat er.
d. Run the pumpout compressor until the suction reaches 15 in. Hg (50 kPa abs). Monitor
pressures on the LID and on r ef rigerant gages.
e. Close valve 6.
f. Turn off pumpout compressor.
g. Close valves 1, 2, and 5 (all v al ves are now closed).
h. Turn off pumpout conden ser water.
i. Continue pumpdown fun ction on the LID to turn off ma c hin e water pumps and lock out
the machine compressor from operation.
Valve 1 2 3 4 5 6 7 8 9 10 11
Condition CC CCCCC