Terminal block connect io ns are provided on the opti ons modules. All sensor in puts are field
wired and installed. Op tions module 1 can be factor y or fi eld-installed. Opt ion s module 2 is
shipped separately and must be field installed. For installation, refer to the unit or field wiring
diagrams. Be sure to add r es s th e module for the proper modu le number (Figure 53) and to
configure the chille r for ea ch feature being used.
Replacing Defective Processor Modules
The replacement part number is printed in a sm all label on front of the PSI O module. The
model and serial numbers are print ed on the unit na meplate located o n an exterior cor ner post.
The proper software is factory-installed by Carrier in the replacement module. When ordering a
replacement processor module (PSIO), specify complete replacement part n umber, full unit
model number, and seri al nu mber. This new unit requ ir es r ec o nfiguration to the ori ginal
machine data by the inst all er. Follow the procedur es de scribed in the Set Up Mach ine Control
Configuration section.

Click here f or Figure 53 — Options Module

CAUTION CAUTION
!
Electrical shock can cause personal injury. Disconnect all electrical power
before servicing.