Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
C. In Recycle Shutdown
Primary Message Secondary Messag e Probable Cause/ Remedy
Recycle Restart
Pending
Occupied Mode Unit in recycle mode, chilled water temperature is not high
enough to start.
Recycle Restart
Pending
Remote Contact Closed Unit in recycle mode, chilled water temperature is not high
enough to start.
Recycle Restart
Pending
Start Command In
Effect Chiller START/STOP on Status01 manually force d to start,
chilled water temper ature is not high enough t o start.
Recycle Restart
Pending
Ice Build Mode Machine in ICE BUILD mode. Chilled Water/Brine Tem-
perature is satisfied for Ice Build Setpoint temper ature.