Suction Temperat ure:
42 F (5.6 C) = 37 psig (255 kPa) saturated refrigerant pressure (HFC-134a)
Condensing Temp erature:
98 F (36.7 C) = 120 psig (1827 k P a) s at urated refrigerant pressure (HFC-134a)
Maximum Load T2:
54 – 44 = 10° F (12.2 – 6.7 = 5.5° C)
Maximum Load P2:
120 – 37 = 83 psid (827 – 255 = 572 kPad )
To avoid unnec essary surge pr evention, add about 10 psid (70 kPad) to P2 from these
conditions:
T2 = 10° F (5.5° C)
P2 = 93 psid ( 642 kPad)