LEAD/LAG TABLECONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY=3 0, 1, 2, 3 0
Load Balance Option Disable/Enable Disable
Common Sensor Option Disable/Enable Disable
LAG Percent Capacity 25 to 75 % 50
LAG Address 1 to 236 92
LAG STARTTimer 2 to 60 Min 10
LAG STOP Timer 2 to 60 Min 10
PRESTARTFAULT Timer 0to30 Min 5
STANDBYChiller Option Disable/Enable Disable
STANDBYPercent Capacity 25 to 75 % 50
STANDBYAddress 1 to 236 93
CL-6