Check Pumpout System Controls and Optional Pumpout Compressor
Controls include an on/ of f switch, a 3-amp fuse, th e compressor overloads, an internal
thermostat, a compressor contactor, and a refrigerant high pressure cutout. The high pressure
cutout is factory set to open at 16 1 psig (1110 kPa) and reset at 130 psig (896 kPa). Check that
the water-cooled condenser has been connected. Loosen the compressor holddown bolts to
allow free spring t ravel. Open the com pressor suction and discharge service valves. Check th at
oil is visible in the compressor sight glass. Add oil if necessary.
See Pumpout and Refrige rant Transfer Proced ures and Pumpout System Maintenance
sections for details on transfer of refrigeran t, oil specifications, etc.
High Altitude Locations
Recalibration of the pre ssure transducers wil l be necessary as the mach ine was initially
calibrated at sea level . Please see the calibrat ion procedure in the Trou bleshooting Guide
section.