Table 8 — LID Primary and Secondary Messages and Custom Alarm/A lert Me ss ag es with Troubleshooting Guides B. Timing Out or Timed Out
Primary Message Secondary Message Probable Cause/ Remedy
Ready To Start In XX
Min
Unoccupied Mode Tim e schedule for PIC is unoccupi ed. Machines will
start only when occupie d.
Ready To Start In XX
Min
Remote Contacts Open Remote contacts have stopped machine. Close co n-
tacts to start.
Ready To Start In XX
Min
Stop Command In Effect Chiller START/STOP on Status01 manually forced to
stop. Release value to st art.
Ready To Start In XX
Min
Recycle Restart Pending Machine in recycle mode.
Ready To Start Unoccupied Mode Time schedule for PIC is UN OCCUPIED. Machine will
start when occupied. Make sure the time and date have
been set on the Service men u.
Ready To Start Remote Contacts Open Remote contacts have stopped machine. Close co n-
tacts to start.
Ready To Start Stop Command In Effect Chiller START/STOP on Status01 manually forced to
stop. Release value to st art.
Ready To Start In XX
Min
Remote Contacts Closed Machine timer coun ting down unit. Ready for start.
Ready To Start In XX
Min
Occupied Mode Machine timer counting do wn unit. Ready for start .
Ready To Start Remote Contacts Close d Machine timers complete, unit start will commence.
Ready To Start Occupied Mode Machine timers comp lete, unit start will co mmence.
Startup Inhibited Loadshed In Effect CCN loadshed module commanding chiller to stop.
Ready To Start In XX
Min
Start Command In Effect Chiller START/STOP on Status01 has been manually
forced to start. Machine will start regardless of time
schedule or remote con tact status.