Control Algorithms Checkout Procedure
In the LID Service menu, one of the tables is Control Al gor it hm Status. This table c on tains 6
tables that may be viewe d in or d er to see how the particul ar control algorithm is ope rating.
These maintenance tabl es are very useful in de te rmining guide vane posi ti on, reaction from
load changes, control point overrides, hot ga s by pas s r ea ction, surge preven tion, etc.
MAINT01
MAINT02
MAINT03
MAINT04
OCCDEFM
WSMDEFME
Capacity Control
Override Status
Surge/HGBP
Status
LEAD/LAG Status
Time Schedules
Status
Water System
Manager Status
This table shows all values that are used to cal culate the
chilled water/bri ne control point.
Details of all chilled wate r control overr ide values are
viewed here.
The surge and hot gas bypass control algorithm stat us is
viewed from this screen. All values dealing with this con-
trol are displayed.
This screen indicates LEAD/LAG operation status.
The Local and CCN occupi ed schedules are displa yed
here in a manner that all ows t he operator to quickly
determine whether the schedule is in the OCCUPI E D
mode or not.
The water system manager is a CCN module which can
turn on the chiller and ch ang e the chilled water cont r ol
point. This screen indicates the status of this system.