Example 13 — Maintenan ce (Maint04) Display S cr een
To access this display f ro m the LID default screen:
1. Press MENU.
2. Press SERVICE.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT.
5. Scroll down to highlight MAINT04.
6. Press SELECT.
Notes:
1. Only values with cap ital letter referenc e point names are var iables available f or read operation. Forcing is
not supported on this m ain tenance screen.
2. = delta degrees.
Table 2, Example 13 — Maintenance (Maint04) Display Screen
Description Range/Status Units Refere nce
Point
Name
LEAD/LAG: Confi gur at i on
Current Mode
Load Balance O ption
LAG Start Time
LAG Stop Time
Prestart Fault Time
Pulldown: Delta T/Min
Satisfie d?
LEAD CHILLER in Control
LAG CHILLER: Mo de
Run Status
Start/St op
Recovery Start Reques t
STANDBY CHILLER: Mode
Run Status
Start/St op
Recovery Start Request
DISABLE, LEAD, LAG, STANDBY, INVALID
DISABLE, LEAD, LAG, STANDBY, CONFIG
DISABLE/ENABLE
0-60
0-60
0-30
x.xx
No/Yes
No/Yes
Reset,Off,Local,CCN
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shut down,Abnormal,Pumpdown
Stop,Start,Retain
No/Yes
Reset,Off,Local,CCN
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shut down,Abnormal,Pumpdown
Stop,Start,Retain
No/Yes
MIN
MIN
MIN
DEG ( DEG C)
leadlag
llmode
loadbal
lagstart
lagstop
preflt
pull dt
pull sat
leadctrl
lagmode
lagstat
lag s s
lag rec
stdmode
stdstat
std s s
std rec