Check Pressure Transducers
Once a year, the pressure tran sducers should be checke d against a pressure gag e re adi ng.
Check all three transduc e rs: oil pressure, conde nser pressure, cooler pr es s u re.
Note the evaporator and condenser pressure readings on the Status01 screen on the LID.
Attach an accurate set of r ef rigeration gages to the coo ler and condenser Sch r ade r fittings.
Compare the two rea dings. If there is a d ifference in readings, the transducer can b e calibrated,
as described in the Troubleshooting Gui de section.
Pumpout System Mainte nance
For compressor maintena nce details, refer to the 06D, 07D Installation, Star t -Up, and
Service Instructions.

Optional Pumpout Compressor Oi l Charge

Use oil conforming to Carr ie r specifications for r ec ip rocating compressor us ag e. Oil
requirements are as fo llo ws:
HFC-134a
ISO Viscosity ................................68
Carrier Part Number ..................PP23BZ103
The total oil charge , 4.5 pints (2.6 L), consists of 3.5 pint s (2.0 L) for the com pressor and one
additional pint (0.6 L) for t he oil separator.