Legend
FLA Full Load Amps
LRA — Locked Rotor Amps
Notes:
1. The oil pump is powered t hr ou gh a field wiring termin al into the power panel.
2. Power to the controls an d oil heater via the power pane l must be on circuits that can provide continuous
service when the compressor starter is disconnected.
Table 16 — Auxiliary Systems, Electrical Data
Power Source Item Supply V-PH-HZ FLA LRA
1
Control Module and
Actuator 115-1-60
115-1-50 3.50
Oil Sump Heater 115-1-60
115-1-50 8.70
2
Oil Pump 200/240-3-60
380/480-3-60
507/619-3-60
4.32
2.15
2.13
24.5
12.2
25.0
220/240-3-50
346/440-3-50 4.83
2.59 28.0
12.2
3 (Optional)
Pumpout Compressor 200/208-3-60
220/240-3-60
440/480-3-60
550/600-3-60
10.9
9.50
4.70
3.80
63.5
57.5
28.8
23.0
380/415-3-50 4.70 28.8