Owner-Modified CCN Tables
The following tables are described for reference only.
Occdef Table Modifications
β€” The Occdef tables contain the Local a nd CCN time
schedules, which can be modified here, or in the Schedule screen as described previously.
Holidef Table Modif ications
β€” The Holidef tabl es configure the da ys of the year that holidays
are in effect. See the hol ida y paragraphs in the Con trols section for more details.
Brodefs Table Modif ications
β€” The Brodefs tab le defines the out side-air temperat ure sensor
and humidity sensor if one is to be installed. It wil l define the start an d end of daylight savings
time. Enter the dates fo r the start and end of dayligh t savings if required for the location.
Brodefs also will act iv at e the Broadcast funct ion which enables the ho liday periods that ar e
defined on the LID.
Other Tables
β€”The Alarmdef, Cons-de f, and Runt-def con ta in tables for use with a CC N
system. See the applicable CCN manual for more information on these tables. These tables can
only be defined through a CC N Building Superv is or .
Check Voltage Supply
Access the Status 01 screen and read the LINE VOLTAGE: ACTUAL value. This reading
should be equal to the incom ing power to the starter. Use a v olt meter to check incomi ng po wer
at the starter power leads . If the readings are not equ al, an adjustment can be made by
selecting the LINE VO LT AGE: ACTUAL point and the n increasing or decre asing the value so