Example 7 — Service1 Disp l ay Screen

To access this display f ro m the LID default screen:

1. Press MENU.
2. Press SERVICE.

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT.

5. Scroll down to highlight SERVICE1.

6. Press SELECT.
Table 2, Example 7 — Service1 Display Screen

Description Configurable

Range Units Reference

Point

Name Default Value

Motor Temp Override*
Cond Press Override
Refrig Override Delta T
Chilled Medium
Brine Refrig Trippoint
Compr Discharge Alert
Bearing Temp Alert
Water Flow Ver ify Time
Oil Press Verify Time
Water/Brine Deadband
Recycle Restart Delt a T
Recycle Shutdown Delta
Surge Limit/HGBP Option
Select: Surge = 0, HGBP = 1
Surge /HGBP Del ta T1
Surge /HGBP Del ta P1
Min. Load Points (T1/P1)
Surge /HGBP Del ta T2
Surge /HGBP Del ta P2
Full Load Points (T2/P2)
Surge/HGBP De adband
Surge Delta Percent Am ps
Surge Time Period
150-200 (66-93)
90-200 (620-1379)
2-5 (1-3)
Water/Brine
8-40 (–13.3-4)
125-200 (52-93)
165-210 (74-99)
0.5-5
15-300
0.5-2.0 (0.3-1.1)
2.0-10.0 (1.1-5.6)
0.5-4.0 (.27-2.2)
0/1
0.5-15 (0.3-8.3)
30-170 (207-1172)
0.5-15 (0.3-8.3)
30-170 (207-1172)
1.3 (0.6-1.6)
10-50
1-5
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
MIN
SEC
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
PSI (kPad)
DEG F (DEG C)
%
MIN
mt over
cp over
ref over
medium
br trip
cd alert
tb alert
wflow t
oilpr t
cw db
rcycrdt
rcycsdt
srg hgbp
hgb dt1
hgb dp1
hgb dt2
hgb dp2
hgb dp
surge a
surge t
200 (93)
125 (862)
3(1.6)
WATER
33 (1)
200 (93)
175 (79)
5
15
1.0 (0.6)
5 (2.8)
1.0 (0.6)
0
1.5 (0.8)
50 (345)
10 (5.6)
85 (586)
1 (0.6)
25
2