Example 8 — Service2 Disp l ay Screen

To access this display f ro m the LID default screen:
1. Press MENU.
2. Press SERVICE.

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT.

5. Scroll down to highlight SERVICE2.

6. Press SELECT.
Table 2, Example 8 — Serv ic e2 Di sp la y S cre en

Description Configurable

Range Units Referen ce

Point

Name

Default

Value
OPTIONS BOARD 1
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source
DEMAND 20 mA Power Source
SPARE ALERT ENABLE
Disable = 0, 1 = High Ale rt, 2 = Low Alert,
3 = High Alarm, 4 = Low Ala rm
Temp = Alert Threshold
CHWS Temp Enable
CHWS Tem p Alert
CHWR Temp Enable
CHWR Te mp Alert
Reset Temp Enable
Reset Temp Alert
Spare Temp 1 Enable
Spare Temp 1 Alert
Spare Temp 2 Enable
Spare Temp 2 Alert
Spare Temp 3 Enable
Spare Temp 3 Alert
0, 1
0, 1
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
res 20 ma
dem 20 ma
chws en
chws al
chwr en
chwr al
rres en
rres al
spr1 en
spr1 al
spr2 en
spr2 al
spr3 en
spr3 al
0
0
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)