d. When all liquid has been push ed int o the utility vessel, close the cooler isolation valv e 7.
e. Access the Control Test, Pumpdown function on the LID display to turn on the machine
water pumps and view the mac h ine pressures.
f. Turn off pumpout compressor.
2. Evacuate refriger ant gas from the cooler/c ond enser/compresso r ves se l.
a. Valve positions: clos e v al ves 2 and 5, open valves 3 and 4.
b. Turn on pumpout conden s er wat er.
c. Run pumpout compressor until the suction reaches 15 in. Hg (50 kPa abs). Monitor
pressures on the LID and on t he refrigerant gages.
d. Close valve 1.
e. Turn off pumpout compressor.
f. Close valves 3, 4, and 6. (All valves are now closed.)
g. Turn off pumpout conden ser water.
h. Continue pumpdown f unction on the LID to t urn off the machine w ater pumps and to lo ck
out the machine compressor from operation.
Valve 1 2 3 4 5 6 7 8 9 10 11
Condition C C CCCCC