Table 8 — LID Primary and Secondary Messages and Custom Alarm/Aler t Mess ages with Troubleshooting Guides F. Start-Up Failures: This is an alarm co ndition. A manual reset is r equired to clear.
Primary
Message Secondary
Message A larm Message/Pri ma ry
Cause Additional Cause/Remedy
Failure To
Start
Low Oil Pressure OILPD [VALUE] exceeded l imit
of [LIMIT]*. Check oil pump sys-
tem.
Check for closed oil s upply valves.
Check oil filter. Check for low oil tem-
perature. Check transd ucer accuracy.
Failure To
Start
Oil Press Sensor
Fault OILPD [VALUE] exceeded limit
of [LIMIT]*. Check oil pressure
sensor.
Check for excessive refrigerant in oil
sump. Run oil pump manuall y for 5 min-
utes. For hermetic compressors, check
both oil pressure and co oler pressure.
For open-drive units, check calibration
of oil pressure diffe rential amplifier
modules. Check wiring. Replace trans-
ducers if necessary.
Failure To
Start
Low Chilled
Water Flow EVFL Evap Flow Fault: C heck
water pump/flow switch. Check wiring to flow switch. Check
through Control Test f or proper switch
operation.
Failure To
Start
Low Condenser
Water Flow CDFL Cond. Flow Fault: Check
water pump/flow switch. Check wiring to flow switch. Check
through Control Test f or proper switch
operation.
Failure To
Start
Starter Fault STR FLT Starter Fault: Check
starter for Fault Source. A start er protective device ha s faulted.
Check starter for grou nd fault, voltage
trip, temperature trip, etc.
Failure To
Start
Starter Overload
Trip STR FLT Starter Overload Trip :
Check amps calibration/reset
overload.
Reset overloads, check ICR relay
before restarting ma chine.
Failure To
Start
Line Voltage
Dropout V P Single-Cycle Dr opout
Detected: Check voltage suppl y. Check voltage supply. C heck trans-
formers for supply. Check with utility if
voltage supply is erratic. Monitor must
be installed to confirm consistent,
single-cycle dropouts. Check low oil
pressure switch.
Failure To
Start
High Condenser
Pressure High Condenser Pressure
[LIMIT]:* Check switch 2C aux,
and water temperature/f low.
Check for proper design co ndenser flow
and temperature. Chec k condenser
approach. Check 2C auxi liary contacts
on oil sump starter. C heck high pres-
sure switch.
Failure To
Start
Excess Accelera-
tion Time CA P Excess Acceleration:
Check guide vane closu re at
start-up.
Check that guide vanes are closed at
start-up. Check starter for proper opera-
tion. Reduce unit press ure if possible.