SERVICE2 TABLECONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
RESET 20 mA Power Source 0/1 0 = EXTERNAL, 1 = INTERNAL 0
DEMAND 20 mAPower Source 0/1 0 = EXTERNAL, 1 = INTERNAL 0
CHWS TempEnable 0to4 0 = DISABLE, 1 = HIGHALERT, 2 = LOW ALERT,
3 = HIGHALARM, 4 = LOW ALARM 0
CHWS TempAlert –40 to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
CHWR TempEnable 0to4 0= DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 = HIGHALARM, 4 = LOW ALARM 0
CHWR TempAlert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Reset TempEnable 0to4 0= DISABLE, 1 = HIGH ALERT, 2 =LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Reset TempAlert –40 to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp1 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp1 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp2 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp2 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp3 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp3 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
SPARE1 20 mA Power Source 0/1 0 =EXTERNAL, 1 = INTERNAL 0
SPARE2 20 mA Power Source 0/1 0 =EXTERNAL, 1 = INTERNAL 0
Spare Temp4 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp4 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp5 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp5 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp6 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp6 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp7 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp7 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp8 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp8 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
Spare Temp9 Enable 0to4 0 =DISABLE, 1 = HIGH ALERT,2 = LOW ALERT,
3 =HIGH ALARM, 4 = LOW ALARM 0
Spare Temp9 Alert –40to 245
(–40 to 118) DEGF
(DEG C) 245
(118)
CL-9