LID Operation and Menus (Fig ure 14, Figure 15, Figure 16, Figure 17, Figure 18, Figure 19, and Figure 20)

General

The LID display will automatically revert to the default screen after 15 minutes if no
softkey activity take s place and if the machine is no t in the Pumpdown mode
(Figure 14).
When not in the default screen, the upper ri ght-hand corner of the LID always dis-
plays the name of the screen that you have entered (F igure 15).
The LID may be configure d in English or SI units, th rough the LID configur at ion
screen.
Local Operation — By pre ssing the LOCAL softke y, the PIC is now in the LOCAL
operation mode a nd the control wi ll accept modi fication to progra mming from the LI D
only. The PIC will use the Lo cal Time Schedule to det ermine machine start and stop
times.
CCN Operation — By pr essing the CCN softk ey, the PIC is now in the CC N operation
mode, and the control will accept modification s from any CCN interfa c e or m odu le
(with the proper author it y), as well as the LID. The P I C will use the CCN time sched -
ule to determine start and st op times.

Click here for Figure 13 — Po wer Panel with Options (Herm et ic Machine Shown)