SERVICE1 TABLECONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Motor Rated Load Amps 1 to 9999 AMPS 200
Motor Rated Line Voltage 1 to 9999 VOLTS 460
Meter Rated Line kW 1to 9999 kW 600
Line Frequency
0=60 Hz/1=50 Hz 0/1 0
Compressor Starter Type REDUCE/FULL REDUCE
Condenser Freeze Point –20 to 35
(–28.9 to 1.7) DEG F
(DEG C) 34
(1.1)
Soft Stop Amps Threshold 40 to 100 % 100
Stop-to-Start Timer* 3to 50 MIN 20
*Open-drive machines only.Standard stop-to-start time for hermetic machines is 3 minutes.
CL-8