Certain conditions dur in g shutdown will change this s eq uence:
if the
COMPRESSOR MOTOR LOAD
is greater than 10% after s hut down, or the
starter contacts rem ain energized, the oil pump and c hi lled water pump remain ene r-
gized and the alarm is dis pla yed
if the
ENTERING CONDENSER WATER
temperature is gr eater than 115 F (46 C) at
shutdown, the condense r pump will be deenergiz ed af ter the 1CR compressor star t
relay
if the machine shuts down due to low ref rigerant temperature , th e ch ill ed water pump
will stay runni ng until the
LEAVING CHILLED WATER
is greater than
CONTROL
POINT
, plus 5° F (3° C)
Automatic Soft Stop Amps Threshold
The SOFT STOP AMPS THRESHOLD closes the guide vanes of the compressor
automatically when a non-recycle, non-alarm stop signal occurs before the compressor motor is
deenergized.
If the STOP button is pres s ed, the guide vanes close to a pre set amperage percent or unt il
the guide vane is less than 2% open. The compressor will then shut off.
If the machine enters an ala rm state or if the compresso r enters a RECYCLE mode, t he
compressor will be deene rgized immediatel y .
To activate SOFT STOP AMPS THRESHOLD, view the bottom of Service1 table. Set the
SOFT STOP AMPS THRESHOLD value to the percentage amps at which the motor will shut
down. The default sett ing is 100% amps (no Soft Stop) .